ActiveIO-LinkM8 hubsOrder code: 78320056
SIOL-M8A-8DON/LSSIOL-M8A-8DON/LS M8 IO-Link hub, 8 NPN digital outputs
SIOL-M8A-8DON/LS is an 8-channel M8 IO-Link hub with 0.2 A NPN digital outputs. It supports IO-Link V1.1 through an M12 A-coded Class A interface and has epoxy resin-potted electronics, shock and vibration resistance, and IP67 protection.
IO-LinkM8 hubsIP67M12NPN







Features
IO-Link remote I/O device
8-channel 0.2 A digital output
IO-Link V1.1
M12 A-coded, IO-Link standard Class A interface
Shock and vibration resistant
Epoxy resin-potted electronics
IP67 protection
Specifications
- Supply voltage
- 24VDC ± 10%
- Operating current
- < 100mA
- Current required for the auxiliary power supply
- < 4A (UL UB) Note: IO-Link Master provides power, Master parameters need to be considered
Output
- Number of channels
- 8 (C0-C7)
- Output type
- The common terminal is 24V (Control 0V)
- Output current
- 0.2A (Max. 0.5A). (UL total max current < 4A)
- Output protection
- Overload protection, overheating protection
- Output protection reaction time
- Approximately 20ms
- Switching frequency
- 100Hz
- Output voltage drop
- ≈ 0.6V
- Electrical Isolation mode
- Optocoupler isolation
IO-Link
- Vendor ID
- 1317 (0x0525)
- Device ID
- 65824(0x010222)
- Number of ports
- 1
- IO-Link specification
- V1.1
- IO-Link port type
- Class A
- Frame type
- TYPE_2_3
- Transmission rate
- COM2 38.4 kbit/s
- Minimum cycle time
- 2400us
- ISDU
- Supported
- Block parameter operation
- Not supported
- Data storage(DS)
- Supported
- Data storage lock
- Supported Note: This function is supported for compatibility, but the device does not perform this operation.
- Operating temperature
- -20...+55°C
Documents
Configuration fileVersion IODD 1.1 / 2024-10-14
SIOL-M8A-8DON/LS IODD file
For models: SIOL-M8A-8DON/LSOrder codes: 78320056Updated: 2026-08-20Size: 53.0 KB
CAD drawing (DWG)
SIOL-M8A-8DON/LS CAD drawing (DWG)
For models: SIOL-M8A-8DON/LSOrder codes: 78320056Updated: 2026-08-20Size: 66.5 KB
3D model (STP)
SIOL-M8A-8DON/LS 3D model (STP)
For models: SIOL-M8A-8DON/LSOrder codes: 78320056Updated: 2026-08-20Size: 629.9 KB
EPLAN
SIOL-M8A-8DON/LS EPLAN
For models: SIOL-M8A-8DON/LSOrder codes: 78320056Updated: 2026-08-20Size: 5.0 MB
Datasheet
SIOL-M8A-8DON/LS datasheet
For models: SIOL-M8A-8DON/LSOrder codes: 78320056Updated: 2026-10-18Size: 1.02 MiB
Accessories
Accessories and connectivity
Published accessory products; open any of them for full details.
Compare models in this series
All M8 hubs (8)| Model | Operating voltage | Current consumption | Supply current | Output channels | View details | |
|---|---|---|---|---|---|---|
![]() | SIOL-M8A-8DON/LSThis model | 24VDC ± 10% | < 100mA | < 4A (UL UB) Note: IO-Link Master provides power, Master parameters need to be considered | 8 (C0-C7) | |
![]() | SIOL-M8-8DIP/LSSame series | 24VDC ± 10% | < 100mA | 1.4A | — | → |
![]() | SIOL-M8A-8DO/LSSame series | 24VDC ± 10% | < 100mA(Ub) | < 4A Note: IO-Link Master provides power, Master parameters need to be considered | 8 (C0-C7) | → |
![]() | SIOL-M8B-8DO/LSSame series | 24VDC ± 10% | < 100mA(Ub) | Not to exceed 4A (Ul) | 8 (C0-C7) | → |